KYN28-12 Saklar Daya Berpakaian Logam Tegangan Menengah
Aug 26, 2022
Parameter teknis utama | |||
Nilai tegangan | ..................................... | kV | 3.6,7.2,12 |
Frekuensi yang dinilai | ..................................... | Hz | 50 |
Nilai arus pemutus sirkuit | ..................................... | A | 630/4000 |
Nilai arus switchgear | ..................................... | A | 630/4000 |
Nilai tahan arus pendek (4S) | ..................................... | kA | 20,25,31.5,40 |
Nilai puncak menahan arus (puncak) | ..................................... | kA | 50,63,80,100 |
Nilai arus pemutus hubung singkat | ..................................... | kA | 20,25,31.5,40 |
Nilai isolasi level 1 menit frekuensi daya menahan tegangan | Kutub-ke-kutub, kutub-ke-tanah | kV | 24,32,42 |
Di antara kontak terbuka | kV | 24,32,48 | |
Impuls petir menahan tegangan (puncak) | Kutub-ke-kutub, kutub-ke-tanah | kV | 40,60,75 |
Di antara kontak terbuka | kV | 46,70,85 | |
Cangkangnya adalah IP4X, dan itu adalah IP2X ketika pintu kompartemen dan pintu ruang pemutus sirkuit dibuka | |||
Ketentuan Layanan
Suhu udara sekitar: -15 derajat ~ ditambah 40 derajat ;
Kelembaban relatif: Rata-rata harian 95 persen,dan rata-rata harian tekanan uap air < 2.2kPa;
Rata-rata bulanan «90 persen , dan rata-rata bulanan tekanan uap air < 1,8kPa;
© Ketinggian: ^1000m;
Intensitas seismik: tidak melebihi Ms8.
Udara sekitar harus bebas dari polusi gas atau uap korosif atau mudah terbakar;
Tidak ada getaran yang jelas;